THE STUDY ON VOLTAGE IMPROVEMENT OF MEDIUM VOLTAGE OVERHEAD WIRE BY TRANSFORMER TAPPING SELECTION

Authors

  • Deksa Mahesa Cipy Sambira Tanjungpura University
  • Junaidi Junaidi Tanjungpura University
  • Rudi Kurnianto Tanjungpura University

DOI:

https://doi.org/10.26418/telectrical.v2i1.78891

Keywords:

tap changer, voltage drop, ETAP software, power transformer, distribution system

Abstract

One of the problems found in the power system is the change or decrease in voltage caused by the power plant center being far from the load center. This study aims to determine the condition of the voltage drop on the Husein Hamzah Feeder and how the use of tap transformers to reduce the voltage drop. The calculation process is simulated using ETAP 19.0.1 software. Based on the simulation results, in the existing condition, the percentage of voltage at the medium voltage bus still meets PLN standards, while at the low voltage bus there are still buses below the standard with a percentage of voltage drop of 3.48%. After making improvements by increasing the transformer tap, the voltage drop value on the bus has decreased to 3.42%. It can be concluded that after making improvements by increasing the transformer tap, the voltage percentage on the rectifier has met SPLN No.72 of 1987 where the percentage of voltage drop does not exceed 5% of the working voltage.

References

A. N. R. Ahmad, S. Sartoni, â€Perbaikan Tegangan Sisi Sekunder Transformator Daya 150KV/20KV di Gardu Induk Ungaranâ€. 2014

A.S. Sampeallo, W.F. Galla, D.M.K Jala,â€Analisis Pengaturan Posisi Tap On Load Tap Changer Pada Transformator Daya 30 MVA 70/20 KV Di GI Maulafaâ€, Jurnal Media Elektro/Vol.VIII/No.2, 2019, doi: https://dx.doi.org/10.35508/jme.v0i0.1886

A. Rafianto, “Analisis Sistem On Load Tap Changer Pada Transformator 150/20 KV Untuk Menjaga Kestabilan Tegangan Pada GI Kaliwungu Jawa Tengahâ€, Media Elektrika, vol.12, no.1, Juni, 2019.

R. T. Tanto, I. Alfi, “Optimalisasi Pengaturan Tegangan Menggunakan Tap Changerâ€, Universitas Teknologi Yogyakarta, 2019

A. N. Afandi, “Operasi Sistem Tenaga Listrik Berbasis EDSAâ€, Gava Media, Yogyakarta, 2010.

Aslimeri, dkk, Teknik Transmisi Tenaga Listrik, Jilid 1, Departemen Pendidikan Nasional, Jakarta, 2008.

M. Ismail, Tenaga Listrik dan Elektronika, Pusat Pengembangan Bahan Ajar-UMB

O. Bishop, Dasar-dasar Elektronika, Erlangga, Jakarta, 2004.

PT. PLN (Persero), “Keputusan Direksi PT. PLN (Persero) No. 474.K/DIR/2010 Sistem Jaringan Tenaga Listrikâ€.

Daryanto, “Teknik Distribusi Tenaga Listrikâ€, PT.Gramedia, Jakarta. 2010.

E.12.6. ETAP 12.6.0 User Guide, User Guide, 2014

R. A. Siregar, “Analisa Perbaikan Profil Tegangan Pada Jaringan Distribusi 20 KV Menggunakan Kapasitor Bank Dan Tap Transformator (Studi Kasus Di GI Sengkaling)â€, Universitas Muhammadiyah Yogyakarta, 2018

D. Dohnal, On-Load Tap-Changers For Power Transformer, Regensburg, Germany, Maschinenfabrik Reinhausen GmbH, 2013

PT. PLN (PERSERO), SPLN No. 72 Tahun 1987 Tentang Spesifikasi Desain Untuk Jaringan Tegangan Menengah (JTM) dan Jaringan Tegangan Rendah (JTR). Jakarta: Departemen Pertambangan dan Energi Perusahaan Umum Listrik Negara.

Syafrijal, R. Monantun, Jaringan Distribusi Tenaga Listrik, Jakarta: Kementerian Pendidikan Dasar Menengah dan Kebudayaan Republik Indonesia, 2014.

T. Gonen, MODERN POWER SYSTEM ANALYSIS, Second edition, Modern Power System Analysis, Second Edition(pp,1-704), CRC Press, 2016, https://doi.org/10.1201/b14796