STUDY OF SIEMENS 7UT86 PERCENTAGE DIFFERENTIAL RELAY AS PROTECTION OF 60 MVA POWER TRANSFORMER AT 150 GIS KV DAYEUH KOLOT

Authors

  • Dian Andreas Purba Universitas Tanjungpura
  • Usman A Gani Universitas Tanjungpura
  • Danial Danial Universitas Tanjungpura

DOI:

https://doi.org/10.26418/telectrical.v2i2.84598

Keywords:

transformer, protection, differential relay, testing

Abstract

Power transformer is a vital equipment in the electric power system that plays an important role in distributing electrical energy from the generator to the load center. Transformers require a protection system that is able to detect an internal or external disturbance with a very fast time to prevent widespread blackouts. Transformer protection generally uses differential relays that require settings in determining their working parameters. On this basis, the authors conducted a study of the Siemens 7UT86 percentage differential relay as a 60 MVA power transformer protection at the 150 kV Dayeuh Kolot GIS, by taking data to perform mathematical calculations to obtain working parameters and testing. The results of mathematical calculations obtained the rating current value used to select the ratio of installed CT to differential current. The relay is set using slope 1 of 30% and slope 2 of 80% and a differential current of 0.3 I/IrObj to prevent unnecessary blackouts due to the appearance of differential currents by magnetizing currents, inrush, tap changers, CT saturation and as a safety factor. Tests using Omicron test equipment obtained results in the form of actual differential current values of both slope areas, angular stability, current and angular ramping and relay operation delay times. Testing the working parameters of the relay obtained the result that the relay works by commanding the circuit breaker to trip when it exceeds the pick up value. During internal faults and at faults below the pick up value and during external faults the relay standsby.

Author Biographies

Dian Andreas Purba, Universitas Tanjungpura

Electrical Engineering Study Program, Faculty of Engineering, Universitas Tanjungpura, Pontianak, Indonesia

Usman A Gani, Universitas Tanjungpura

Department of Electrical Engineering, Faculty of Engineering, Universitas Tanjungpura, Pontianak, Indonesia

Danial Danial, Universitas Tanjungpura

Department of Electrical Engineering, Faculty of Engineering, Universitas Tanjungpura, Pontianak, Indonesia

References

P. M. Anderson, Power System Protection. Piscataway, NJ: Wiley Interscience, 1999.

N. Prasetyo, “Analisa Pengaturan Proteksi Rele Differensial Pada Transformator Daya II Gardu Induk Kota Baru,†Vol 10, No: Juli 2022. https://jurnal.untan.ac.id/index.php/j3eituntan/search/search?simpleQuery=nanang&searchField=query

Riswanto Septi Yaldo dan Zulkarnaini, “Studi Analisis relay Differensial Pada Proteksi Transformator 60 MVA GIS Simpang Haru,†Pros. Semin. Nas. Sains dan Teknol., pp. 603–607, 2021.

K. Deuria, “Analisis Penggunaan Rele Diferensial Di PLTMG Sumbagut 2 Peaker Power Plant 250 MW,†J. Energi List., vol. 10, pp. 9–13, 2021.

J. Duncan, T. J. Overbye, and M. S. Sarma, Power System Analysis and Design, Sixth edit. Boston: Cengage learning, 2017.

W. H. W. W. G. Hurley, Transformers and Inductors for Power Electronics. Noida, India, 2013.

M. J. Heathcote, The J&P Transformer Book, Thirteenth. Chennai: Elsevier Ltd, 2007.

K. R. M. Nair, Power & Distribution Transformers Practical Design Guide. Boca Raton, FL: CRC Press LLC, 2021.

PT. PLN (Persero), Pedoman Pemeliharaan Proteksi dan Kontrol Transformator. Jakarta, 2014.

B. M. V. Bakshi U. A., Protection and Switchgear. Pune: Technical Publications Pune, 2006.

Harlow James H., Electric Power Transformer Engineering. Florida: CRC Press LLC, 2004.

Kadir Abdul, Transformator. Jakarta: Penerbit Universitas Indonesia, 2010.

L. Tobing Bonggas, Peralatan Tegangan Tinggi, Edisi 2. Medan: Penerbit Airlangga, 2012.

S. W. Fardo and D. R. Patrick, Electrical Power Systems Technology 3 ed, vol. 84. 2013.

P. A. G. Horowitz Standlay H., Power System Relaying, Fourth Edi. Chichester, United Kingdom: John Wiley and Sons Ltd, 2014.

R. A. Robert M. Del Vecchio, Bertrand Poulin, Pierre T. Feghali, Dilipkumar M. Shah, Transformer Design Principles, Third Edit. Boca Raton, FL: CRC Press, 2018.

Siemens, “SIPROTEC 4 Differential Protection,†Nuremberg, 2016.

Mohamed Ibrahim, Transformer differential protection testing. Bahrain, 2021.

OMICRON electronics, “CMC 356 The Universal Relay Test Set and Commissioning Tool,†2022.

OMICRON electronics, “Testing Solutions for Protection, Automation and Control Systems - Product Catalog,†p. 68, 2020, [Online]. Available: https://www.omicronenergy.com/en/products/state-sequencer/.

Downloads

Published

2024-11-25

Issue

Section

Articles