STUDI SUSUT UMUR TRANSFORMATOR DISTRIBUSI 20 kV AKIBAT PEMBEBANAN LEBIH DI PT.PLN (PERSERO) KOTA PONTIANAK
DOI:
https://doi.org/10.26418/j3eit.v5i3.21155Abstract
Abstract
Distribution transformer has a very crucial role on electrical power supply distribution system. In 1972, International Electrotechnical Commission (IEC) 354 claim if a transformer get a stable load on it"™s identification power with ambient temperature 200C, transformer hot spot temperature will reach 980C and it"™s lifetime became 20 years or 7300 days with
normal loss of life 0,0137% each day.
Daily average ambient temperature in Pontianak is 300C, causing transformer"™s load has to be adjust to avoid high
loss of life. Distribution transformer which installed on feeder Raya 10 has 11 units operating with daily load 80% - 100%
of identification power and 8 units with over 100% daily load of identification power. Base on research that has been done we"™ve come to conclusion that transformer which operating in Pontianak should not gain 91% load of identification power cause will decreasing the transformer lifetime drasticly.
Keywords: distribution transformer, loss of life, ambient temperature, load.
Downloads
Published
Issue
Section
License
Authors who publish with this journal agree to the following terms:
- Copyright of the published articles will be transferred to the journal as the publisher of the manuscripts. Therefore, the author confirms that the copyright has been managed by the publisher.
- Publisher of J3EIT is Universitas Tanjungpura.
- The copyright follows Creative Commons Attribution"“ShareAlike License (CC BY SA): This license allows to Share "” copy and redistribute the material in any medium or format, Adapt "” remix, transform, and build upon the material, for any purpose, even commercially.
Journal of Electrical Engineering, Energy, and Information Technology by Universitas Tanjungpura is licensed under CC BY-SA 4.0