Seismic Performance Evaluation of an Eight-Story Reinforced Concrete Apartment Building with Special Moment-Resisting Frame in Kubu Raya Regency

Authors

  • Fagan Resha Santana Department of Civil Engineering, Tanjungpura University
  • Gatot Setya Budi Department of Civil Engineering, Tanjungpura University
  • M. Yusuf Department of Civil Engineering, Tanjungpura University

DOI:

https://doi.org/10.26418/jts.v26i1.97408

Keywords:

Seismic performance assessment, Special moment-resisting frame (SMRF), Nonlinear stiffness reduction, Response spectrum method, Inter-story drift.

Abstract

This study presents the structural analysis and seismic performance evaluation of an eight-story reinforced concrete apartment building in Kubu Raya Regency, Indonesia, designed using a Special Moment Resisting Frame (SMRF) system. The design follows the seismic and detailing requirements of SNI 1726:2019 and SNI 2847:2019. A three-dimensional finite element model was developed in ETABS, with beams and columns modeled as frame elements and slabs as shell elements, incorporating stiffness-reduction factors to represent cracked-section behavior. Structural analysis considered gravity, wind, and seismic loads in accordance with SNI 1727:2020 and SNI 1726:2019. Seismic performance was evaluated using response spectrum analysis, ensuring at least 90% modal mass participation in each principal direction. Performance checks included inter-story drift limits, earthquake force scaling, P-Delta effects, and horizontal and vertical irregularities. The results show that all seismic performance criteria are satisfied, with inter-story drifts within allowable limits and stable structural behavior. Reinforcement detailing for all structural components complies with SMRF requirements, ensuring adequate ductility. The foundation system using driven piles was verified based on site-specific SPT data. Overall, the structural system demonstrates sufficient strength, stiffness, and seismic reliability.

References

Aburrokhim, I. A., Sutriono, B., & Triana, M. I. (2023). Review Kinerja Struktur Atas Gedung Reskrimsus Polda Jawa Timur Berdasarkan Peraturan Sni 1726-2019 Dan Sni 2847-2019. Jurnal Ilmiah Teknik dan Manajemen Industri, 3(1), 753-760.

Ala, B., Elvira, & Faisal. (2023). Perhitungan Struktur Bangunan Gedung Kantor di Kabupaten Mempawah. JeLAST, 10(3), 1–6.

American Concrete Institute. (2015). Building Code Requirements for Structural Concrete (ACI 318M-14) and Commentary (ACI 318RM-14). American Concrete Institute.

Anugerah, F. A., Supriyadi, A., & Elvira. (2024). Perancangan Struktur Beton Bertulang Gedung Tujuh Lantai Mal Pelayanan Publik dengan SRPMB di Kabupaten Sambas. JeLAST, 11(2), 1–6.

Anwar, J. A., & Andaryati. (2024). Perencanaan Struktur Beton Bertulang Hotel “Dracarys” 13 Lantai dengan Sistem SRPMK di Kota Depok. Jurnal Rekayasa Dan Manajemen Konstruksi, 12(2), 93–104.

Badan Standardisasi Nasional. (2019). Persyaratan Beton Struktural untuk Bangunan Gedung dan Penjelasan (SNI 2847:2019).

Badan Standardisasi Nasional. (2019). Tata Cara Perencanaan Ketahanan Gempa untuk Struktur Bangunan Gedung dan Nongedung (SNI 1726:2019).

Badan Standardisasi Nasional. (2020). Beban Desain Minimum dan Kriteria Terkait untuk Bangunan Gedung dan Struktur Lain (SNI 1727:2020).

Barus, D., & Chairina, E. (2024). Evaluasi Struktur Balok Dan Hubungan Balok dengan Kolom sesuai SNI 2847: 2019 pada Proyek Pembangunan Gedung Parkiran Kantor UPPD Medan Utara. Jurnal Teknik Sipil, 3(1), 62–67.

Figo, L., Yusuf, M., & Supriyadi, A. (2025). Application of Intermediate Moment-Resisting Frame for Seven-Story Hotel Structure Building in Pontianak. Jurnal Teknik Sipil, 25(1), 1811–1827.

Hakika, I. K., Elvira, & Yusuf, M. (2024). Design of Reinforced Concrete Structure of 6-story Ayani Square Office Shop Building with Intermediate Moment Resisting Frame System. Jurnal Teknik Sipil, 24(3), 1139–1151. https://doi.org/10.26418/jts.v24i3.82742

Hardiyatmo, H. C. (2010). Analisis dan Perancangan Fondasi (Bagian II). Gadjah Mada University Press.

Hukom, V., Sutiono, W., Purwantoro, A. D. S., & Fajar, M. N. (2023). Analisis Perbandingan Penulangan Dinding Geser Berdasarkan Tata Cara Sni 2847: 2013 Dengan Sni 2847: 2019, Studi Kasus: Hotel Vega Kota Sorong. Jurnal Ilmiah Teknik Sipil (JIMATS), 2(1), 001–012.

Khotimah, H., Rosyidah, A., Saputra, J., Rinawati, & Sucita, I. K. (2023). Performance of Seismic-Resistant Building Structure Using Diaphragm Based on SNI 2847: 2019 and ACI 318-19. In Global Congress on Manufacturing and Management (pp. 192–206). Cham: Springer Nature Switzerland.s

Lesmana, Y. (2020). Handbook Desain Struktur Beton Bertulang Berdasarkan SNI 2847-2019 (1st ed.). Nas Media Pustaka.

Lesmana, Y. (2021). Handbook Analisa Dan Desain Struktur Tahan Gempa Beton Bertulang (SRPMB, SRPMM, & SRPMK) Berdasarkan SNI 2847-2019 & 1726-2019 (1st ed.). Nas Media Pustaka.

Lubis, F., & Apriani, W. (2024). Evaluation of building structure planning using SNI 1726: 2019 and SNI 2847: 2019 in earthquake-prone areas. In IOP Conference Series: Earth and Environmental Science (Vol. 1321, No. 1, p. 012024). IOP Publishing.

Lunardi, F., Aryanto, & Yusuf, M. (2024). Design of 8-story Reinforced Concrete Structure of Wangguh Apartment Pontianak Building with Comparison of Beam Review. Jurnal Teknik Sipil, 24(1), 736–752.

Manik, J. F. (2024). Evaluation of the Strength of Reinforced Concrete Beams in the Construction of Phase II Social Institution Building in Medan According to SNI 2847: 2019 and SNI 1726: 2019 (Case Study). Jurnal Mekintek: Jurnal Mekanikal, Energi, Industri, Dan Teknologi, 15(1), 07–12.

Mentari, C. P. R., Alami, F., & Sebayang, S. (2022). Studi ketebalan minimum pelat beton bertulang menurut SNI 2847: 2019 terhadap kenyamanan manusia. REKAYASA: Jurnal Ilmiah Fakultas Teknik Universitas Lampung, 26(2), 34–39.

Maharani, D., Budi, G. S., & Faisal. (2024). Perancangan Struktur Beton Bertulang Rumah Susun Tujuh Lantai Tahan Gempa di Kota Pontianak. JeLAST, 11(2), 1–10.

Nadiar, F., Zega, B. C., Dani, H., Suprapto, S., Sari, S. F. M., Prasetyono, P. N., & Zulfikar, A. R. (2024). Comparative analysis of deviation in high buildings based on earthquake load SNI 1726: 2012 and SNI 1726: 2019. In E3S Web of Conferences (Vol. 513, p. 01008). EDP Sciences.

Patria, A. S. N. (2021). Perbandingan Parameter Spektrum Respons Desain SNI 1726:2012 dengan SNI 1726:2019 pada 39 Kabupaten/Kota di Pulau Jawa. Jurnal Kacapuri, 4(1), 126–134.

Pratiwi, A., Supriyadi, A., & Faisal. (2022). Perencanaan Struktur Beton Bertulang Gedung 7 Lantai Tahan Gempa Lokasi Jalan Letjend Suprapto Kota Pontianak. JeLAST, 9(1), 1–8.

Puspabella, F., Sutandar, E., & Yusuf, M. (2022). Perhitungan Struktur Beton Bertulang Gedung 7 Lantai Sekolah Santu Petrus dengan Sistem Rangka Pemikul Momen. JeLAST, 9(1), 1–9.

Rahman, F. N. F., & Khatulistiani, U. (2024). Sistem Rangka Pemikul Momen Khusus (SRPMK) untuk Perencanaan Struktur Beton Bertulang Gedung Hotel “Lustrio” di Kota Mataram. Jurnal Rekayasa Dan Manajemen Konstruksi, 12(3), 147–160.

Rahmanto, F., Elvira, & Supriyadi, A. (2023). Calculation of the Institut Teknologi dan Bisnis Sabda Setia Kota Pontianak Building’s Structure. Jurnal Teknik Sipil, 23(1), 1–14.

Rizik, A. F., Soelarso, S., Baehaki, B., & Darwis, Z. (2024). Analysis of Optimization of Cross-Sections and Reinforcement of Building Structures Based on SNI 2847-2019 and SNI 1726-2019. Fondasi: Jurnal Teknik Sipil, 13(2), 168–179.

Santoso, A. N., & Astawa, M. D. (2022). Performance Evaluation of 34 Floors Building Structure in Surabaya Based on Sni 1726: 2012 and Sni 1726: 2019. Jurnal Teknik Sipil, 18(2), 185–201.

Saputra, M. A., Budi, G. S., & Yusuf, M. (2025). Implementation of Special Moment Resisting Frame for the Design Structure of a Seven-Story Academic Building in Pontianak. Jurnal Teknik Sipil, 25(1), 1828–1845. https://doi.org/10.26418/jts.v25i1.89

Sutiono, T., Budi, G. S., & Herwani. (2023). Calculation Of Earthquake Resistant Structure Of Medical Center Building Rumah Sakit Umum Daerah (RSUD) Soedarso Pontianak Using Pushover Analysis. Jurnal Teknik Sipil, 23(3), 337–349.

Wardi, S., & Ardiansyah, S. Y. (2022). Perbandingan Ketentuan dan Analisis Detailing Hubungan Balok-Kolom Berdasarkan SNI 2847: 2013 dan SNI 2847: 2019. Borneo Engineering: Jurnal Teknik Sipil, 6(2), 159–170.

Wight, J. K., & MacGregor, J. G. (2012). Reinforced Concrete Mechanics and Design (6th ed.). Pearson Education, Inc.

Zhafira, T., Kurniawan, I. B., Purwanto, P., Hidayat, M. F., & Prayuda, H. (2023). The Structure Analysis of Five Floor Mall Building in Semarang City According to SNI 1726-2019 and SNI 2847-2019. Journal of Civil Engineering and Planning (JCEP), 4(1), 1–13.

Zulshaec, Y., Herwani, & Yusuf, M. (2024). Design of Reinforced Concrete Structure with Ordinary Moment Frame in Low Seismic Region (Case Study: Midrise Shopping Building in Singkawang City). Jurnal Teknik Sipil, 24(1), 721–735.

Downloads

Published

2026-02-09

Issue

Section

Vol 26, No 1 (2026): Vol 26, No 1 (2026): Jurnal Teknik Sipil (JTS) Universitas Tanjungpura, Edisi Februari 2026